Quality and satisfaction of thermal comfort in Dutch offices

Onderzoeksoutput: Contribution to conference proceedingAcademicpeer review

Uittreksel

Purpose: This field study analyses the quality of the actual thermal comfort and indoor air quality in Dutch office buildings. A linear regression analysis was used to determine how much these variables and demographic variables influenced the perceived thermal comfort of office workers.
Approach: Data were collected on-spot at two Dutch office buildings (n=182) during the winter of 2015 and showed that the indoor air in these offices is of good quality and did not affect the perceived thermal comfort significantly. The indoor temperature was the most important variable that influenced the perceived thermal comfort. Indoor temperatures ranged in this study from 18 till 24oC and were therefore at the edge of acceptable European and Dutch standards NPR-CR 1752 (1999), NEN-EN 15251(2007) and NEN-EN-ISO 7730 (2007).
Findings: Office workers which experienced a indoor temperature of 20oC graded this temperature the highest (6.7 on a scale from 1-10). At 20oC the percentage of workers that was dissatisfied was the lowest (30%). This study also showed that female workers were more likely to have the sensation that is was too cold than male workers. European and Dutch standards prescribe that an indoor temperature between 21 and 23oC should be the most ideal temperature during wintertime. This study indicates that an indoor temperature higher than 22oC might be too warm for office workers in The Netherlands during wintertime and that application might influence office workers’ satisfaction negatively.
Originele taal-2English
TitelResearch Papers: 15th EuroFM Research Symposium
RedacteurenS. Balslev Nielsen, P.A. Jensen
UitgeverijEuroFM: European Facility Management Network
Pagina's162-171
ISBN van geprinte versie9788750211020
StatusPublished - 2016

Keywords

  • thermisch comfort
  • binnentemperatuur
  • luchtkwaliteit
  • kantoorgebouwen

Citeer dit

Brink, H. W., & Mobach, M. P. (2016). Quality and satisfaction of thermal comfort in Dutch offices. In S. Balslev Nielsen, & P. A. Jensen (editors), Research Papers: 15th EuroFM Research Symposium (blz. 162-171). EuroFM: European Facility Management Network.
Brink, Henk Willem ; Mobach, Mark P. / Quality and satisfaction of thermal comfort in Dutch offices. Research Papers: 15th EuroFM Research Symposium. redacteur / S. Balslev Nielsen ; P.A. Jensen. EuroFM: European Facility Management Network, 2016. blz. 162-171
@inproceedings{646ccf47fffd42f2a5b290b9bffcccd0,
title = "Quality and satisfaction of thermal comfort in Dutch offices",
abstract = "Purpose: This field study analyses the quality of the actual thermal comfort and indoor air quality in Dutch office buildings. A linear regression analysis was used to determine how much these variables and demographic variables influenced the perceived thermal comfort of office workers.Approach: Data were collected on-spot at two Dutch office buildings (n=182) during the winter of 2015 and showed that the indoor air in these offices is of good quality and did not affect the perceived thermal comfort significantly. The indoor temperature was the most important variable that influenced the perceived thermal comfort. Indoor temperatures ranged in this study from 18 till 24oC and were therefore at the edge of acceptable European and Dutch standards NPR-CR 1752 (1999), NEN-EN 15251(2007) and NEN-EN-ISO 7730 (2007).Findings: Office workers which experienced a indoor temperature of 20oC graded this temperature the highest (6.7 on a scale from 1-10). At 20oC the percentage of workers that was dissatisfied was the lowest (30{\%}). This study also showed that female workers were more likely to have the sensation that is was too cold than male workers. European and Dutch standards prescribe that an indoor temperature between 21 and 23oC should be the most ideal temperature during wintertime. This study indicates that an indoor temperature higher than 22oC might be too warm for office workers in The Netherlands during wintertime and that application might influence office workers’ satisfaction negatively.",
keywords = "thermal comfort, indoor temperature, air quality, office buildings, thermisch comfort, binnentemperatuur, luchtkwaliteit, kantoorgebouwen",
author = "Brink, {Henk Willem} and Mobach, {Mark P.}",
year = "2016",
language = "English",
isbn = "9788750211020",
pages = "162--171",
editor = "{Balslev Nielsen}, S. and P.A. Jensen",
booktitle = "Research Papers: 15th EuroFM Research Symposium",
publisher = "EuroFM: European Facility Management Network",

}

Brink, HW & Mobach, MP 2016, Quality and satisfaction of thermal comfort in Dutch offices. in S Balslev Nielsen & PA Jensen (redactie), Research Papers: 15th EuroFM Research Symposium. EuroFM: European Facility Management Network, blz. 162-171.

Quality and satisfaction of thermal comfort in Dutch offices. / Brink, Henk Willem; Mobach, Mark P.

Research Papers: 15th EuroFM Research Symposium. redactie / S. Balslev Nielsen; P.A. Jensen. EuroFM: European Facility Management Network, 2016. blz. 162-171.

Onderzoeksoutput: Contribution to conference proceedingAcademicpeer review

TY - GEN

T1 - Quality and satisfaction of thermal comfort in Dutch offices

AU - Brink, Henk Willem

AU - Mobach, Mark P.

PY - 2016

Y1 - 2016

N2 - Purpose: This field study analyses the quality of the actual thermal comfort and indoor air quality in Dutch office buildings. A linear regression analysis was used to determine how much these variables and demographic variables influenced the perceived thermal comfort of office workers.Approach: Data were collected on-spot at two Dutch office buildings (n=182) during the winter of 2015 and showed that the indoor air in these offices is of good quality and did not affect the perceived thermal comfort significantly. The indoor temperature was the most important variable that influenced the perceived thermal comfort. Indoor temperatures ranged in this study from 18 till 24oC and were therefore at the edge of acceptable European and Dutch standards NPR-CR 1752 (1999), NEN-EN 15251(2007) and NEN-EN-ISO 7730 (2007).Findings: Office workers which experienced a indoor temperature of 20oC graded this temperature the highest (6.7 on a scale from 1-10). At 20oC the percentage of workers that was dissatisfied was the lowest (30%). This study also showed that female workers were more likely to have the sensation that is was too cold than male workers. European and Dutch standards prescribe that an indoor temperature between 21 and 23oC should be the most ideal temperature during wintertime. This study indicates that an indoor temperature higher than 22oC might be too warm for office workers in The Netherlands during wintertime and that application might influence office workers’ satisfaction negatively.

AB - Purpose: This field study analyses the quality of the actual thermal comfort and indoor air quality in Dutch office buildings. A linear regression analysis was used to determine how much these variables and demographic variables influenced the perceived thermal comfort of office workers.Approach: Data were collected on-spot at two Dutch office buildings (n=182) during the winter of 2015 and showed that the indoor air in these offices is of good quality and did not affect the perceived thermal comfort significantly. The indoor temperature was the most important variable that influenced the perceived thermal comfort. Indoor temperatures ranged in this study from 18 till 24oC and were therefore at the edge of acceptable European and Dutch standards NPR-CR 1752 (1999), NEN-EN 15251(2007) and NEN-EN-ISO 7730 (2007).Findings: Office workers which experienced a indoor temperature of 20oC graded this temperature the highest (6.7 on a scale from 1-10). At 20oC the percentage of workers that was dissatisfied was the lowest (30%). This study also showed that female workers were more likely to have the sensation that is was too cold than male workers. European and Dutch standards prescribe that an indoor temperature between 21 and 23oC should be the most ideal temperature during wintertime. This study indicates that an indoor temperature higher than 22oC might be too warm for office workers in The Netherlands during wintertime and that application might influence office workers’ satisfaction negatively.

KW - thermal comfort

KW - indoor temperature

KW - air quality

KW - office buildings

KW - thermisch comfort

KW - binnentemperatuur

KW - luchtkwaliteit

KW - kantoorgebouwen

M3 - Contribution to conference proceeding

SN - 9788750211020

SP - 162

EP - 171

BT - Research Papers: 15th EuroFM Research Symposium

A2 - Balslev Nielsen, S.

A2 - Jensen, P.A.

PB - EuroFM: European Facility Management Network

ER -

Brink HW, Mobach MP. Quality and satisfaction of thermal comfort in Dutch offices. In Balslev Nielsen S, Jensen PA, redacteurs, Research Papers: 15th EuroFM Research Symposium. EuroFM: European Facility Management Network. 2016. blz. 162-171