Long-term infiltration performance evaluation of dutch permeable pavements using the full-scale infiltration method

Floris Boogaard, Terry Lucke

Research output: Contribution to journalArticleProfessional

Abstract

This research used a newly developed, full-scale infiltration testing (FSIT) procedure to determine the saturated surface infiltration rate of 16 existing permeable pavement installations in the Netherlands that have been in service for a number of years. Newly installed permeable pavements in the Netherlands must demonstrate a minimum infiltration capacity of 194 mm/h (540 L/s/ha). Only four of the 16 pavements tested in this study had an infiltration capacity higher than 194 mm/h. Most previous research has focused on unsaturated infiltration rates. However, the results of this study show that the difference in infiltration capacity between saturated and unsaturated can differ by up to 300%. If the unsaturated infiltration capacity is used as design input for computer models, the infiltration capacity may be significantly overestimated. The study demonstrated that the FSIT method is a reliable and accurate way to measure surface infiltration rates of permeable pavements. However, it is recommended that a minimum of three different FSIT tests should be undertaken at the same pavement location, and that the results should be averaged, to ensure appropriate infiltration rates are observed, recorded, and used in design. The results of this study should help stormwater managers with the planning, testing, and scheduling of maintenance requirements for permeable pavements with more confidence so that they will continue to perform satisfactorily over their intended design life
Original languageEnglish
JournalWater
Volume11
Issue number2
DOIs
Publication statusPublished - 14 Feb 2019

Keywords

  • permeable pavement
  • infiltration rate
  • clogging
  • full-scale test method
  • monitoring

Cite this

@article{1bcae150039148fe874426c2c9d90f09,
title = "Long-term infiltration performance evaluation of dutch permeable pavements using the full-scale infiltration method",
abstract = "This research used a newly developed, full-scale infiltration testing (FSIT) procedure to determine the saturated surface infiltration rate of 16 existing permeable pavement installations in the Netherlands that have been in service for a number of years. Newly installed permeable pavements in the Netherlands must demonstrate a minimum infiltration capacity of 194 mm/h (540 L/s/ha). Only four of the 16 pavements tested in this study had an infiltration capacity higher than 194 mm/h. Most previous research has focused on unsaturated infiltration rates. However, the results of this study show that the difference in infiltration capacity between saturated and unsaturated can differ by up to 300{\%}. If the unsaturated infiltration capacity is used as design input for computer models, the infiltration capacity may be significantly overestimated. The study demonstrated that the FSIT method is a reliable and accurate way to measure surface infiltration rates of permeable pavements. However, it is recommended that a minimum of three different FSIT tests should be undertaken at the same pavement location, and that the results should be averaged, to ensure appropriate infiltration rates are observed, recorded, and used in design. The results of this study should help stormwater managers with the planning, testing, and scheduling of maintenance requirements for permeable pavements with more confidence so that they will continue to perform satisfactorily over their intended design life",
keywords = "permeable pavement, infiltration rate, clogging, full-scale test method, monitoring, watermanagement",
author = "Floris Boogaard and Terry Lucke",
year = "2019",
month = "2",
day = "14",
doi = "https://doi.org/10.3390/w11020320",
language = "English",
volume = "11",
journal = "Water",
issn = "2073-4441",
publisher = "MDPI",
number = "2",

}

Long-term infiltration performance evaluation of dutch permeable pavements using the full-scale infiltration method. / Boogaard, Floris; Lucke, Terry.

In: Water, Vol. 11, No. 2, 14.02.2019.

Research output: Contribution to journalArticleProfessional

TY - JOUR

T1 - Long-term infiltration performance evaluation of dutch permeable pavements using the full-scale infiltration method

AU - Boogaard, Floris

AU - Lucke, Terry

PY - 2019/2/14

Y1 - 2019/2/14

N2 - This research used a newly developed, full-scale infiltration testing (FSIT) procedure to determine the saturated surface infiltration rate of 16 existing permeable pavement installations in the Netherlands that have been in service for a number of years. Newly installed permeable pavements in the Netherlands must demonstrate a minimum infiltration capacity of 194 mm/h (540 L/s/ha). Only four of the 16 pavements tested in this study had an infiltration capacity higher than 194 mm/h. Most previous research has focused on unsaturated infiltration rates. However, the results of this study show that the difference in infiltration capacity between saturated and unsaturated can differ by up to 300%. If the unsaturated infiltration capacity is used as design input for computer models, the infiltration capacity may be significantly overestimated. The study demonstrated that the FSIT method is a reliable and accurate way to measure surface infiltration rates of permeable pavements. However, it is recommended that a minimum of three different FSIT tests should be undertaken at the same pavement location, and that the results should be averaged, to ensure appropriate infiltration rates are observed, recorded, and used in design. The results of this study should help stormwater managers with the planning, testing, and scheduling of maintenance requirements for permeable pavements with more confidence so that they will continue to perform satisfactorily over their intended design life

AB - This research used a newly developed, full-scale infiltration testing (FSIT) procedure to determine the saturated surface infiltration rate of 16 existing permeable pavement installations in the Netherlands that have been in service for a number of years. Newly installed permeable pavements in the Netherlands must demonstrate a minimum infiltration capacity of 194 mm/h (540 L/s/ha). Only four of the 16 pavements tested in this study had an infiltration capacity higher than 194 mm/h. Most previous research has focused on unsaturated infiltration rates. However, the results of this study show that the difference in infiltration capacity between saturated and unsaturated can differ by up to 300%. If the unsaturated infiltration capacity is used as design input for computer models, the infiltration capacity may be significantly overestimated. The study demonstrated that the FSIT method is a reliable and accurate way to measure surface infiltration rates of permeable pavements. However, it is recommended that a minimum of three different FSIT tests should be undertaken at the same pavement location, and that the results should be averaged, to ensure appropriate infiltration rates are observed, recorded, and used in design. The results of this study should help stormwater managers with the planning, testing, and scheduling of maintenance requirements for permeable pavements with more confidence so that they will continue to perform satisfactorily over their intended design life

KW - permeable pavement

KW - infiltration rate

KW - clogging

KW - full-scale test method

KW - monitoring

KW - watermanagement

UR - http://www.mendeley.com/research/longterm-infiltration-performance-evaluation-dutch-permeable-pavements-using-fullscale-infiltration

U2 - https://doi.org/10.3390/w11020320

DO - https://doi.org/10.3390/w11020320

M3 - Article

VL - 11

JO - Water

JF - Water

SN - 2073-4441

IS - 2

ER -